URI-II

Uri-II power station is run-of-the-river scheme with an installed capacity of 240 MW (4 X 60 MW) to harnesses the Hydropower potential of river Jhelum (a tributary of Indus river). The Power Station was commissioned in year the 2013-14.The layout plan features and photo gallery of the Power Station are detailed below.
Feature Name | Description |
---|---|
Approach | Nearest Airport: Srinagar, Nearest Rail Head: Udhampur/Jammu |
Location | Baramulla District, Union Territory of J&K |
Capacity | 240 MW |
Design Energy | 1123.77 (90 % dependable year with 95% machine availability) |
Beneficiary States/UTs | Jammu & Kashmir, Punjab, Delhi, Himachal Pradesh, Haryana, Rajasthan, Uttar Pradesh, Uttarakhand & Chandigarh |
Date of Commercial Operation (COD) | U#1- 11/10/2013 U#2 - 01/12/2013 U#3 - 11/10/2013 U#4 - 01/03/2014 |
Dam | |
Type | Concrete gravity Dam: |
Height | 52 m |
Length | 157 m |
FRL: | 1241 m |
MDDL | 1241 m |
HRT: | |
Type | Horse-shoe shaped. |
Diameter | 8.4 m |
Length | 4.28 Km |
Pressure Shaft | |
No’s of Pressure shaft | 2 no. |
Type | Circular steel lined |
Diameter | 5 m internal dia (from surge shaft to branching) |
TRT/Tail pool | |
Type | Horse-shoe shaped. |
Diameter | 8.4 m |
Length | 3.637 Km |
TWL | 1111 m |
Power House | |
Type | Under Ground |
Capacity | Comprising of four units of 60 MW each. |
Turbine | |
Type | Francis |
Rated head | 118 m |
Design discharge | 225 m3/sec (for all 04 units) |
Number of guide vanes | 20 |
Generator | |
Rated Continuous output | 67 MVA |
Rated Voltage | 11 kV |
No of Poles | 20 |
Rated speed | 300 RPM |
Generator Step up Transformer (GSU) | |
Type | Indoor; Single-Phase |
Voltage Ratio | 11/400/√3 kV |
Rated MVA | 25 MVA |
Type of cooling | OFWF |
Switchyard/Pot head yard | |
Type | GIS |
Voltage level | 400 kV |
No. of lines | 02 |
URI-II -Wagoora URI-II-URI-I | |